Proof
Tested by an independent lab, warranted for 50 years.
The numbers an architect, engineer or inspector asks for, with the report numbers, and the warranty conditions in full.
112.5 psf
ASTM E330 overload, no failure
<0.01
cfm per sq ft air infiltration, ASTM E283
15 psf
dynamic water penetration, pass, AAMA 501.1
50 yr
panel warranty
Wall assembly tests
Air, water and structure.
The assembly tests used a 48 by 96 inch wall of 2x4 studs at 16 inches on center, 7/16 inch OSB sheathing, a water vapor barrier, 1 inch R-5 XPS continuous insulation, Speedymason panels in the modular configuration fastened with #8 by 2-1/2 inch stainless screws at 8 inches on center, Speedymason mortar mix and 3/8 inch modular thin brick, cured 28 days before testing.
How the wall handles the water these tests push at it, layer by layer, is on Where the water goes.
| Test | Standard | Result | Report |
|---|---|---|---|
| Air infiltration | ASTM E283-12 | Under 0.01 cfm per sq ft at 1.57 psf. | 102860812MID-006 8 May 2017 |
| Water penetration, static pressure | ASTM E331-16 | Pass. No leakage at 11.28 psf. | 102860812MID-006 8 May 2017 |
| Structural performance, uniform static load | ASTM E330-14 | Design pressure plus and minus 75 psf. Overload plus and minus 112.5 psf held 30 seconds with no signs of failure. | 102860812MID-006 8 May 2017 |
| Water penetration, dynamic pressure | AAMA 501.1-05 | Pass. No leakage at 15 psf for 15 minutes. | 102860812MID-009 26 April 2017 |
Panel tests
The panel on its own.
| Test | Standard | Result | Report |
|---|---|---|---|
| Fastener pull-through resistance | ASTM D1037-12, section 15 | Nails 116.9 lbf average (S.D. 5.5). Screws 109.5 lbf average (S.D. 3.3).No factor of safety applied; not for design. | 102860812MID-003 21 February 2017 |
| Water vapor transmission and permeance | ASTM E96-16 | 0.18 perms (S.D. 0.06). 0.08 grains/h per sq ft. | 102860812MID-004 28 March 2017 |
Tests were run by an independent evaluation laboratory in Middleton, Wisconsin, in 2017, on samples it selected at the plant. The full reports, with sample descriptions and drawings, are in the submittal package.
Fire
Fire performance.
A wall of thin brick on Speedymason has been through the two fire tests building officials ask about, and it passed both.
Passed NFPA 285
NFPA 285 is the fire test the building code calls for on the outside walls of many multi-story buildings. A full wall of thin brick on Speedymason panels was burned for 30 minutes on March 28, 2023, and it passed. The tested wall was 18-gauge 3-5/8 in. steel studs at 24 in. on center, 1/2 in. exterior glass-mat sheathing, a commercial building wrap, 3 in. of continuous insulation board, the Speedymason Rainscreen and Brick Lath, a full bed of polymer-modified thin set, clay thin brick and grouting/pointing mortar. The result belongs to that wall, so match it or ask before you specify.
No flame spread, no smoke
On ASTM E84 the finished wall, which is the panel, the mortar bed and the brick, scored 0 for flame spread and 0 for smoke. That is the best score the test gives, and it is a Class A rating.
Ask us for a report when a submittal or a building official needs one.
Report numbers and full results
| ASTM E84-16 | Surface burning of the finished wall: Speedymason panel, full bed of mortar and thin brick, brick face to the flame, two runs102860812SAT-020A and -021A, 17 and 18 May 2017 | Flame spread index 0, smoke developed index 0, both runs. That is the Class A range (flame spread 0 to 25, smoke 0 to 450). |
|---|---|---|
| ASTM E84-16 | Surface burning of the bare panel alone, no mortar or brick102860812SAT-002A and -016A, 16 February 2017 | Flame spread 135 and 130, smoke developed 500 and 450. The panel is always covered by mortar and brick in a finished wall. |
| NFPA 285 | Fire test of the full exterior wall assembly, the test the code calls for on many multi-story buildings: steel studs, glass-mat sheathing, building wrap, 3 in. continuous insulation, Speedymason Rainscreen and Brick Lath, thin set, clay thin brickTested wall assembly drawing in the downloads; ask Speedymason for the report, 28 March 2023 | Passed. Specify the tested assembly, or ask Speedymason before changing it. |
From the field
“I am beyond impressed on the amount of deflection the Speedymason system could take without the brick falling off.”
Zach Stackhouse, Store Engineering Project Manager, Kwik Trip
After a car ran into a Kwik Star store (Kwik Trip's Iowa brand), the thin brick stayed on the wall.
A field observation, not a test. Speedymason publishes no impact or windborne-debris rating.
Warranty
The 50-year panel warranty.
The Speedymason composite panel is warranted free from defects in material under normal use and service for fifty years from the date of original delivery.
Speedymason repairs or replaces the product to bring it into compliance. The warranty covers the panel alone, not the brick, mortar, fasteners or labor, and liability is limited to the unit price of the defective product.
What keeps it in force
- The panel is installed in accordance with the Speedymason Product and Installation Guide.
- The buyer registers the project within 90 days of completed installation: project name, address and building type, start and completion dates, buyer, architect, installer and general contractor details with signatures, a copy of the purchase order, and at least six photos of the stages of the project including the finished building.
- Defects caused by abuse, improper maintenance, structural defects, building settlement or movement, corrosive materials, fire, flood or unapproved alteration are not covered.
Code
Adhered veneer limits the wall must meet.
Speedymason is the backing. The wall design still has to sit inside the TMS 402-22 chapter 13 prescriptive limits, and some states amend them. The engineer of record owns the design.
| Unit thickness | Not more than 2-5/8 in. |
|---|---|
| Unit face area | Under 720 sq in. (an approved installation procedure is required above 360 sq in.) |
| Unit weight | Under 30 psf |
| Assembly weight | Under 50 psf |
| Height | Not more than 60 ft above the grade plane |
| Backing | Vertical only; sheathing required on frame backing |
| Depth | Exterior face to back of scratch coat under 4-5/8 in. |
Standards in the specification
What the guide spec references.
- ASTM C1088, thin veneer brick units made from clay or shale, Grade Exterior, Type TBS, TBX or TBA
- ASTM C1935, standard practice for installing thin brick in adhered veneer, which covers brick set in mortar or adhesive on a modular support system
- ASTM C1714 and ASTM C270 with ANSI A118.4 shear bond: polymer-modified thin set for the setting bed, and grouting/pointing mortar, Type S or Type N, for the joints between the bricks
- TMS 602 / ACI 530.1 / ASCE 6, specification for masonry structures
- ASTM B117, 800 hours of salt spray protection on screw fasteners
- Section 04 25 16, Mortar Bed Panel System for Thin Masonry, in the editable Word guide specification
Questions
What specifiers ask.
Is Speedymason tested?
Yes. An independent laboratory tested the panel for fastener pull-through (ASTM D1037) and vapor permeance (ASTM E96), and tested a full wall assembly for air infiltration (ASTM E283), water penetration (ASTM E331 and AAMA 501.1) and structural load (ASTM E330). The report numbers and results are on this page and the full reports are in the submittal package.
Has Speedymason passed a fire test?
Yes. A full wall of thin brick on Speedymason panels passed NFPA 285, the exterior wall fire test, in March 2023. On ASTM E84 the finished wall scored 0 for flame spread and 0 for smoke developed, which is the best score the test gives. Ask Speedymason for the reports when a submittal needs them.
What wind load has the assembly held?
In ASTM E330 testing the wall assembly held plus and minus 75 psf design pressure and plus and minus 112.5 psf overload for 30 seconds each with no signs of failure. Design loads for a project are set by the engineer of record.
What does the 50-year warranty cover?
Defects in material in the Speedymason composite panel itself, for fifty years from delivery, when the panel is installed per the installation guide and the project is registered within 90 days. The remedy is repair or replacement of the panel.
Does Speedymason meet the code for adhered veneer?
Speedymason is the backing for an adhered veneer wall. The wall design still has to meet TMS 402 chapter 13 limits on unit size, weight and height, and local amendments. The limits are listed on this page and the guide specification references TMS 602.
Patents
Two United States patents.
The panel and its guide legs are covered by a utility patent; the panel's appearance by a design patent. Both name Shane Calmes as inventor.
| Number | Kind | Title | Granted |
|---|---|---|---|
| US 10,106,989 B2 | Utility patent | Apparatus for setting objects | October 23, 2018 |
| US D860,479 S | Design patent | Architectural panel | September 17, 2019 |