Water management

Where the water goes.

Rain that gets past the brick and mortar runs down the water-resistive barrier behind the Speedymason panel, held off by the dimples on the panel's back, and leaves at the base flashing. The panel is the backing for the brick. It does not replace the barrier or the flashing, and the wall is designed on the assumption that some water always gets in.

11.28 psf

static water penetration, no leakage, ASTM E331

15 psf

dynamic water penetration, 15 minutes, pass, AAMA 501.1

<0.01

cfm per sq ft air infiltration, ASTM E283

0.18

perms, the panel on ASTM E96

The layers

From the studs to the weather, in order.

Each layer has one job with water. The panel sits in the middle and its job is to keep a path open behind the brick.

  1. 1

    Framing and sheathing

    Wood or steel studs with exterior-grade sheathing, 5/8 inch preferred, 7/16 inch the minimum. On concrete or block there is no sheathing.

  2. 2

    Water-resistive barrier

    Building wrap, a sealer or a fluid-applied membrane over the sheathing, lapped shingle fashion and tied into the flashing. The code requires it on frame walls. The panel does not replace it.

  3. 3

    Continuous insulation, when the wall has it

    Rigid foam or mineral wool between the barrier and the panel. The tested wall carried 1 inch of R-5 XPS. Fastener length follows the thickness.

  4. 4

    The Speedymason panel

    Dimples on the back face the barrier, so water that reaches the barrier runs down it with the panel held off by the dimples. The factory rainscreen option adds a 3/8 inch drainage and ventilation layer for walls designed to drain.

  5. 5

    Polymer-modified thin set

    The full bed behind each brick, keyed in behind the guide legs. A specialty polymer-modified thin set on Stone Lath and Ultra-Speed.

  6. 6

    Thin brick and grouting/pointing mortar

    The face the weather hits. Fired clay and tooled mortar joints absorb some rain and give most of it back as the wall dries. Ultra-Speed sets the brick tight with no mortar joint.

The layers of the tested Speedymason wall, labeled from the framing to the brick
The dimpled back of a Speedymason panel with the rainscreen mesh
The back of the panel: dimples that stand it off the barrier, and the factory rainscreen layer on panels ordered with it.

Barrier or drainage

The honest answer to the question masons ask.

Speedymason's product data calls the panel a barrier system like metal lath, with drainage built in. That is two claims, and both are true in a specific way.

Every panel: a path down the barrier

The dimples on the back of the panel hold it off the water-resistive barrier. Water that gets through the brick and the thin set reaches the barrier and runs down it to the base flashing, the way it would behind metal lath and a scratch coat, with the panel standing off instead of lying flat. The panel does not absorb water and does not rust.

With the rainscreen: a drainage and ventilation gap

For a wall the architect designs to drain and dry behind the veneer, the factory-applied rainscreen adds a 3/8 inch (10 mm) layer to the back of the panel. Water drains down it and air moves through it, and it arrives on the panel, so the drainage plane is one step fewer on site. It is available on 16 by 48 inch Brick Lath and Stone Lath.

The rainscreen panel

The Aloft Hotel in West Chester, Ohio, with thin brick above a stone base

On a building

At the Aloft Hotel in West Chester, Ohio, 19,894 square feet of thin brick on Brick Lath sit above 7,400 square feet of stone on Stone Lath. Because both panels share one water plane behind them, moisture weeps out at the bottom of the wall, and the flashing that would normally separate the stone from the brick was not needed.

The Aloft case study

Flashing

Where the water leaves, and where it must not get in.

From the Speedymason detail sheets. The full sets, 48 sheets for Brick Lath and 26 for Stone Lath, are on the details page.

On the job

  • Install the barrier and the flashing before the first panel, to the code and the Speedymason detail sheets. The dimples on the back of the panel act as a watershed over the barrier.
  • Flash and caulk every opening and every termination. Water finds the one that was skipped.
  • Control joints every 15 feet, or as the architect calls out, with backer rod and a flexible sealant. A sealed joint moves; a mortared one cracks and lets water in.
  • On concrete or masonry substrates the guide specification does not require a barrier. Follow the project documents and local code.
  • Clean the finished wall with the brick maker's cleaner, 5 to 10 days after bagging, without flooding it.

All wall detailsWood frame install guide

What the 2017 tests measured

The assembly tests used a 48 by 96 inch wall of 2x4 studs at 16 inches on center, 7/16 inch OSB sheathing, a water vapor barrier, 1 inch R-5 XPS continuous insulation, Speedymason panels in the modular configuration fastened with #8 by 2-1/2 inch stainless screws at 8 inches on center, Speedymason mortar mix and 3/8 inch modular thin brick, cured 28 days before testing.

Air and water test results for the Speedymason wall assembly
Air infiltrationASTM E283-12Under 0.01 cfm per sq ft at 1.57 psf.
Water penetration, static pressureASTM E331-16Pass. No leakage at 11.28 psf.
Water penetration, dynamic pressureAAMA 501.1-05Pass. No leakage at 15 psf for 15 minutes.

Independent laboratory, Middleton, Wisconsin. Report numbers are on the testing page. These results are for the Brick Lath assembly, not for Ultra-Speed.

Questions

Water, answered.

Does Speedymason need a water-resistive barrier?

Yes, on every exterior frame wall. The installation guide calls for a code-approved air and water barrier over the sheathing, and the panel's drainage dimples work over it. On concrete and masonry the guide specification leaves the barrier to the project documents.

Is a Speedymason wall a barrier wall or a drainage wall?

Speedymason's product data calls the panel a barrier system like metal lath, with drainage built in: the dimples on the back give water a path down the barrier to the base flashing. For a wall the architect designs to drain and ventilate, the factory-applied rainscreen adds a 3/8 inch layer behind the panel. The wall design and the climate decide which, and the architect owns that call.

Does water get behind thin brick?

Some always does, on any masonry veneer. Brick and mortar absorb rain and dry out again, and sealant joints age. The system is designed on that assumption: a barrier behind the panel, a drainage path along it and flashing that puts the water back outside.

Does the panel trap water?

The back of the panel is dimpled, so it stands off the barrier instead of lying flat against it, and the panel itself does not absorb water. The tested assembly showed no leakage at 11.28 psf static and 15 psf dynamic pressure.

When do I specify the rainscreen?

When the wall is designed to drain and ventilate behind the veneer, in a wet or wind-driven-rain climate, or wherever the architect wants a defined drainage gap. The rainscreen comes applied to the back of 16 by 48 inch Brick Lath and Stone Lath panels, so it adds no step on site.

Is the panel a vapor retarder?

The panel measured 0.18 perms on ASTM E96, which falls in the Class II vapor retarder range the building code defines (over 0.1 and up to 1.0 perm). Whether that is right for the wall depends on the climate and what else is in the assembly, so the wall designer checks the condensation potential, especially with continuous insulation.

What goes wrong when the water is not managed: freeze-thaw, efflorescence and the rest

Next step

A wall section to review?

Send the detail and the climate zone. We will mark up where the barrier, the panel and the flashing go.