Fire

Thin brick and NFPA 285.

Speedymason Brick Lath passed NFPA 285 on March 28, 2023, as part of a full exterior wall: steel studs, glass-mat sheathing, building wrap, 3 inches of continuous insulation, Speedymason Rainscreen and Brick Lath, polymer-modified thin set, clay thin brick and joint mortar. NFPA 285 tests a whole wall assembly, not a product, so a specifier uses the tested assembly or asks Speedymason before changing it.

The tested wall

What was in the wall that passed.

From the inside out, as drawn on the tested assembly sheet.

  1. 118-gauge 3-5/8 in. steel studs at 24 in. on center
  2. 21/2 in. exterior glass-mat sheathing
  3. 3Commercial building wrap
  4. 43 in. polyisocyanurate continuous insulation board
  5. 5Speedymason Rainscreen
  6. 6Speedymason Brick Lath
  7. 7Polymer-modified thin set
  8. 8Clay thin brick
  9. 9Grouting/pointing mortar joints

Result: Passed. Specify the tested assembly, or ask Speedymason before changing it. Date: 28 March 2023.

Tested wall drawing (PDF)Ask for the report

The Speedymason wall standing in the NFPA 285 test rig, March 28, 2023
The Speedymason wall in the test rig, March 28, 2023.

Surface burning

ASTM E84, the finished wall and the bare panel.

  • Surface burning of the finished wall: Speedymason panel, full bed of mortar and thin brick, brick face to the flame, two runs

    Flame spread index 0, smoke developed index 0, both runs. That is the Class A range (flame spread 0 to 25, smoke 0 to 450).

    Report 102860812SAT-020A and -021A, 17 and 18 May 2017.

  • Surface burning of the bare panel alone, no mortar or brick

    Flame spread 135 and 130, smoke developed 500 and 450. The panel is always covered by mortar and brick in a finished wall.

    Report 102860812SAT-002A and -016A, 16 February 2017.

Every test, with report numbers

Questions

NFPA 285, answered.

What is NFPA 285?

A fire test of a whole exterior wall assembly: a two-story wall is exposed to a fire from a room burner and a window burner for 30 minutes, and the test measures whether flame spreads up the face, across the wall or through the cavity. It applies to walls that contain combustible parts such as foam insulation or certain water-resistive barriers.

When does the building code require NFPA 285?

The International Building Code calls for it on exterior walls of Type I, II, III and IV buildings that contain foam plastic insulation, and on walls of those buildings more than 40 feet above grade that contain a combustible water-resistive barrier, with exceptions. Local amendments vary, so check the adopted code.

Has Speedymason passed NFPA 285?

Yes. A Speedymason Brick Lath wall with Rainscreen over 3 inches of continuous insulation passed on March 28, 2023. The tested wall drawing is in the downloads, and Speedymason supplies the report on request.

Is a product "NFPA 285 approved"?

No product is. NFPA 285 results belong to the tested assembly. Changing the insulation, the barrier or the sheathing changes the assembly, so check with Speedymason or an engineering judgment before substituting.

What about ASTM E84?

The finished Speedymason wall, panel plus full bed of mortar plus thin brick, scored 0 flame spread and 0 smoke developed on ASTM E84, the Class A range. The bare panel alone, which is never exposed in a finished wall, scored 135 and 130 flame spread.

Installing over continuous insulation

Next step

Specifying a multi-story wall?

Ask for the NFPA 285 report and the tested assembly before the wall section is final.